Your Source for Process Measurement & Control
UK
44-796-072-6366
Germany
49-178-631-1266
Relative Humidity-Ambient Temperature Transmitters
HX94B
PLACE ORDER - RoHS Certified
- Accurate to ±2.5% Relative Humidity and ±0.6°C (±1°F) Temperature
- Two Separate Analog Outputs, Humidity and Temperature
- Four Analog Outputs available, 4 to 20 mA, 0 to 1V, 0 to 5V, 0 to 10V
- Stainless Steel NEMA 4 (IP66) Enclosure
- Three Different Output Connection Styles Available
- Includes Hardware for Wall and Duct Mounting
- Removable Stainless Steel Sensor Cap
Description
Description
The trodeks® HX94B Seriestemperature/relative humiditytransmitter provides a linearized andtemperature compensated outputsignal of 4 to 20 mA, 0 to 1 Vdc,0 to 5 Vdc or 0 to 10 Vdc dependingupon the model selected for bothtemperature/relative humiditymeasurement. The output signalshave been calibrated and scaled to0 to 100°C for temperature and0 to 100% for relative humidity.The digital temperature and relativehumidity sensor is protected by astainless steel cap that is easilyremoved for cleaning. The NEMA 4stainless steel enclosure and cableentry connection provides weathertight protection. The stainless steelenclosure terminates to a 6 feetshielded cable. The cable end iseither stripped leads or terminatesto a 4-pin connector.
Specifications
Temperature
Measuring Range: 0 to 100°C (32°F to 212°F)
Accuracy: ±0.6°C from 0 to 50°C (32 to 122°F), ±1.25°C from 50 to 100°C (122 to 212°F)
Repeatability: ±0.2°C (0.4°F)
Response Time: 5 seconds minimum, 30 seconds maximum
Sample Rate: 1 sample every 4 seconds
Relative Humidity
Measuring Range: 0 to 100% RH
Accuracy: ±2.5 % from 20 to 80% RH, ±3.5% from 5 to 20% and 80 to 95% RH, ±4% from 0 to 5% and 95 to 100% RH
Hysteresis: ±1%RH
Repeatability: ±0.1%RH
Response Time: 8 seconds typical
Sample Rate: 1 sample every 4 seconds
Operating Temperature Range: 0 to 100°C (32 to 212°F)
Analog Outputs for Temperature and Humidity: 4 to 20 mA, 0 to 1V, 0 to 5V, 0 to 10V
Input Power Supply: 9 to 30 Vdc @ 100 mA: 4 to 20 mA, 0 to 1V, 0 to 5V output, 12 to 30 Vdc @ 100 mA: 0 to 10V output
Max Current Loop Resistance: Ω = [(V supply - 4V)/0.02A)] -50; 200Ω @ 9V supply or 1250Ω @ 30V supply
Max Load Resistance: 1.25K (for all voltage outputs)
Sensor Type: Digital sensor
Enclosure Housing: 316 stainless steel, NEMA 4; non-NPT version includes IP68-rated cable gland
Electrical Connections:
HX94B**W, HX94B**NPT: 1.8 m (6') 4 conductor PTFE shieldedcable with stripped leads termination
HX94B**: 1.8 m (6') 4 conductor PTFE shielded cable with a 4-pin connector termination; a 4-pin mating connector is included that accepts 18 to 26 AWG wire
Dimensions: 258 L x ø19 mm OD (10.15 x 0.75")
Weight: 200 g (7 oz) with mounting kit Anemometer | Automation | Accelerometers | Calibrator | Cartridge Heaters | Chart Recorders | Cryogenics | Custom Pressure Transducers | Data Loggers | Data Acquisition | Dial Thermometers | Fiber Optics | Fiber Optic Temperature Measurement | Flexible Heaters | Flow Meters | Glass Bulb Thermometers | Grippers | Heaters | Humidity Measurement | Integrated Circuit Sensors | Immersion Heaters | Infrared Thermometers | Level Measurement | Load Cells | M12 Temperature Connectors | Magnetic Flow Meter | Panel Meter | PID Controllers | pH meter | Pressure Gauges | Pressure Transducers | Pressure Transmitters | Rotameters | RTD | Remote Process Monitoring | Sanitary Sensors | Signal Conditioners | Stepper Motors | Strain Gages | Strip Heaters | Temperature Controllers | Temperature Labels | Temperature Measurement | Temperature Sensor Manufacturing | Temperature Sensors | Temperature Transmitters | Thermal Imagers | Thermistors | Thermocouple | Thermocouple Wire | Thermowell | Ultrasonic Flow Meters | Vortex Flow Meter | Wireless Sensors
trodeks.comtrodeks.com - فقخیثنس.زخئ - صصص.فقخیثنس.زخئ