Your Source for Process Measurement & Control
UK
44-796-072-6366
Germany
49-178-631-1266
Product Groups
1-16 DIN High-Low Limit Controller
TRODEKS Engineering | Thermocouples, Pressure Transducers, Flow Meters, PID Controllers
CN63500 Series
PLACE ORDER 
  • Dual 4-Digit LED Display
  • Thermocouple or RTD Sensor Input
  • Remote Reset Input
  • Main Limit Output: 5 A Relay, Selectable for High or Low Trip Activiation
  • 5 A Relay Alarms (Optional)
  • Parameters Security Via Programmable Lockouts
  • FM, UL, and cUL Approved
 Specs
 Manuals (contact with email : [email protected])
 Print
Description

Description

The CN63500 Series are temperature limit controllers,intended to provide an independent shutdown forthermal processes. The CN63500 accepts signalsfrom a variety of temperature sensors (thermocouple orRTD elements),and its comprehensive programmingallows it to meet a wide variety of applicationrequirements. Dual 4-digit displays allow viewing of theprocess temperature and limit setpoint simultaneously.Front panel indicators inform the operator of theprocess and output status. The main limit output andalarm outputs are field-replaceable. The limit output isselectable for high or low trip activation. If the processtemperature goes above the limit setpoint for a hightrip, or below the limit setpoint for a low trip, the limitrelay will de-energize to initiate a process shutdown.The limit output cannot be reset until the processtemperature returns to the proper operating range;manual reset is required (local or remote). Sensorfailure will initiate a process shutdown. Relay alarm(s)can be configured to activate according to a variety ofactions (absolute high or low, deviation high or lowand band in or out) with adjustable hysteresis. Astandby feature suppresses the alarm during power-upunit the process stabilizes outside the alarm region.The unit is constructed of lightweight, high-impactplastic case with a tinted front panel. the front panelmeets NEMA 4X (IP65) specifications when properlyinstalled. Multiple units can be stacked horizontally orvertically. Modern surface-mount technology,extensive testing, plush high-immunity to noiseinterference makes the CN63500 extremely reliable inindustrial environments.

Thermocouple
Type
Display
Range
Wire Color
ANSI BS1843
T -200 to 400°C
-328 to 752°F
(+) Blue
(-) Red
(+) White
(-) Blue
E -200 to 750°C
-328 to 1382°F
(+) Violet
(-) Red
(+) Brown
(-) Blue
J -200 to 760°C
-328 to1400°F
(+) White
(-) Red
(+) Yellow
(-) Blue
K -200 to 1250°C
-328 to 2282°F
(+) Yellow
(-) Red
(+) Brown
(-) Blue
R 0 to 1768°C
32 to 3214°F
(+) Black
(-) Red
(+) White
(-) Blue
S 0 to 1768°C
32 to 3214°F
(+) Black
(-) Red
(+) White
(-) Blue
B 149 to 1820°C
300 to 3308°F
(+)Grey
(-)Red
No standard
N -200 to 1300°C
-328 to 2372°F
(+) Orange
(-) Red
(+) Orange
(-) Blue
mV -5.00 to 56.00mV No standard No standard
 
RTD Type Range
385 -200 to 600°C (-328 to 1100°F)
392 -200 to 600°C (-328 to 1100°F)
Ω 2.0 to 320.0Ω
SPECIFICATIONS
Display: 2-line by 4-digit LED
Upper (Main) Display: 10.2 mm (0.4") H red LED
Lower (Secondary) Display: 7.6 mm (0.3") H green LED
Power:
    Line Voltage Models: 85 to 250 Vac, 50/60 Hz, 8 VA
    Low-Voltage Models:
       DC Power: 18 to 36 Vdc,7W
       AC Power: 24 Vac ±10%, 50/60 Hz, 9 VA
Memory: Non-volatile E2PROM retains all programmable parameters and values

Environmental Conditions
Operating Range: FM rated @ 0 to 65°C, UL rated @ 0 to 55°C
Storage Range: -40 to 80°C (-40 to 176°F)
Operating and Storage Humidity: 85% max relative humidity (non-condensing) from 0°C to 65°C (32 x 149°F)
Altitude: Up to 2000 m

Isolation Breakdown Ratings
AC Line With Respect to All Inputs and Outputs: 2300 V for 1 minute (250 V working)
Relay Contacts to All Other Inputs and Outputs: 2300 Vac
DC Power With Respect to Sensor Input: 50 V working (500 V for 1 minute)
Connection: Wire clamping screw terminals
Weight: 0.17 kg (0.38 lb)

Input Specifications
Sensor Input
Sample Period: 100 ms
Step Response Time: Less than 300 ms typical, 400 ms max (to within 99% of final value)
Normal Mode Rejection: >40 dB @ 50/60 Hz
Common Mode Rejection: >120 dB, DC to 60 Hz
Overvoltage Protection: Input overload 120 Vac for 15 s max
Failed Sensor Response:
    Main Output: Sensor failure will initiate a process shutdown
Display: "OPEN"
Alarms: Upscale
Indication Accuracy: ±(0.3% of span +1°C) @ 23°C ambient after 20 minute warm-up (includes NIST conformity, cold-junction effect, A/D conversion errors and linearization conformity
Span Drift (Maximum): 130 PPM/°C
Rtd Input: 2- or 3-wire, 100 Ù platinum, alpha = 0.00385 (DIN43760), alpha = 0.0039162
Excitation: 150 A typical
Lead Resistance: 15 Ω max per input lead
Remote Resent Input: Internally pulled up to 5 Vdc 1 mΩ
    VIL: 0.85 V max
    VIH: 3.65 V min
    VIN Max: 5.25 Vdc
    IOFF:1 µA max

Output Specifications
Limit and Alarm Output Relays
Contact Rating: 5 A @ 250 Vac or 30 Vdc (resistive load) 1/10 HP @ 120 Vac (inductive load)
Life Expectancy: 100,000 cycles at max load rating (decreasing load increases life expectancy)
Limit Output:
    CN63500-R1-AL1: Form "C" relay
    CN63500-R1-AL2: Form "A" relay
Selectable for high or low trip activation, if the process temperature goes above the limit setpoint for a high trip, or below the limit setpoint for a low trip, the limit relay will deenergize to initiate a process shutdown; the limit output cannot be reset until the process temperature returns to the proper operating range; manual reset is required (local or remote)
AlarmOutputs: 1 or 2 form "A" relays
Modes: Absolute high-acting, absolute low-acting, deviation high-acting, deviation low-acting, inside band-acting, outside band-acting
Reset Action: programmable, automatic or latched; latched alarms can be reset regardless of limit exceed condition
Standby Mode: Programmable, enable or disable
Hysteresis: Programmable

Thermocouple Inputs
Types: T, E, J, K, R, S, B, N, linear mV, software selectable
Input Impedance: 20 MΩ, all types
Lead Resistance Effect: 0.25 µV/Ω
Cold-Junction Compensation: <±1°C typical, (±1.5°C max), error over 0 to 65°C (32 to 149°F) max ambient temperature range; defeated for linear mV indication mode
Resolution: 1° for all types, or 0.1° for T, E, J, K, and N only
Anemometer  |   Automation  |   Accelerometers  |   Calibrator  |   Cartridge Heaters  |   Chart Recorders  |   Cryogenics  |   Custom Pressure Transducers  |   Data Loggers  |   Data Acquisition  |   Dial Thermometers  |   Fiber Optics  |   Fiber Optic Temperature Measurement  |   Flexible Heaters  |   Flow Meters  |   Glass Bulb Thermometers  |   Grippers  |   Heaters  |   Humidity Measurement  |   Integrated Circuit Sensors  |   Immersion Heaters  |   Infrared Thermometers  |   Level Measurement  |   Load Cells  |   M12 Temperature Connectors  |   Magnetic Flow Meter  |   Panel Meter  |   PID Controllers  |   pH meter  |   Pressure Gauges  |   Pressure Transducers  |   Pressure Transmitters  |   Rotameters  |   RTD  |   Remote Process Monitoring  |   Sanitary Sensors  |   Signal Conditioners  |   Stepper Motors  |   Strain Gages   |   Strip Heaters  |   Temperature Controllers  |   Temperature Labels  |   Temperature Measurement  |   Temperature Sensor Manufacturing  |   Temperature Sensors  |   Temperature Transmitters  |   Thermal Imagers  |   Thermistors  |   Thermocouple  |   Thermocouple Wire | Thermowell  |   Ultrasonic Flow Meters  |   Vortex Flow Meter  |   Wireless Sensors