Digital High Voltage Insulation Tester
TRODEKS Engineering | Thermocouples, Pressure Transducers, Flow Meters, PID Controllers
HHM-380395 Series
PLACE ORDER 
  • Test Voltages of 500V, 1000V, 2500V, and 5000V
  • Measure Insulation Resistance to 60G Ù
  • Large 6000 Count Display with Bargraph and Backlight
  • Polarization Index Measurement (PI)
  • Dielectric Absorption Ratio Measurement (DAR)
  • AC/DC Voltage Measurement from 0 to 600V with Max/Min, Peak and Relative Functions
  • 1 to 15 Minute Timer Function for Insulation Resistance Measurements
  • Resistance Measurement
  • Indication of Output Voltage and Discharge Voltage
  • Auto-Discharge Function and Voltage Output Warning Function
  • Autoranging, Auto Power-Off and Battery Check
 Specs
 Manuals (contact with email : [email protected])
 Print
Description

Description

The HHM-380395 meter providesfour insulation resistance testranges plus continuity, AC/DC voltage, polarization indexand dielectric absorption ratiomeasurements. This meter isshipped fully tested and calibrated,with proper care and use, willprovide years of reliable service.

Specifications
Display: 6000 count LCD display with bargraph
Sampling Rate: 2.5 times per second
Over Range Indication: “OL” appears on the LCD
Short Circuit Current: >200 mA
Open Circuit Test Voltage: >4.5V
Low Battery Indication: Battery symbol appears on the LCD
Power Supply: Eight (8) 1.5V “C” cell batteries (included) or 13.5V 1A AC adaptor
Fuse: 500 mA/600V (6 x 32 mm) ceramic 3AG fast blow
Auto Power Off: After approximately 20 minutes of inactivity
Operating Temperature: 0 to 40°C (32 to 104°F)
Operating Humidity: < 80% RH
Altitude: Up to 2000 meters (6562 feet)
Storage Temperature: -10 to 60°C (14 to 140°F )
Storage Humidity: < 80% RH
Dimensions: 198 H x 148 W x 86 mm Diameter (7.8 x 5.8 x 3.4")
Weight: Approx. 1438 g (50.7 oz) with battery
Safety Standards/Ratings: Pollution degree 2, meets IEC 61010-1 and IEC 61010-031
Category Rating: CAT IV 600V
Anemometer  |   Automation  |   Accelerometers  |   Calibrator  |   Cartridge Heaters  |   Chart Recorders  |   Cryogenics  |   Custom Pressure Transducers  |   Data Loggers  |   Data Acquisition  |   Dial Thermometers  |   Fiber Optics  |   Fiber Optic Temperature Measurement  |   Flexible Heaters  |   Flow Meters  |   Glass Bulb Thermometers  |   Grippers  |   Heaters  |   Humidity Measurement  |   Integrated Circuit Sensors  |   Immersion Heaters  |   Infrared Thermometers  |   Level Measurement  |   Load Cells  |   M12 Temperature Connectors  |   Magnetic Flow Meter  |   Panel Meter  |   PID Controllers  |   pH meter  |   Pressure Gauges  |   Pressure Transducers  |   Pressure Transmitters  |   Rotameters  |   RTD  |   Remote Process Monitoring  |   Sanitary Sensors  |   Signal Conditioners  |   Stepper Motors  |   Strain Gages   |   Strip Heaters  |   Temperature Controllers  |   Temperature Labels  |   Temperature Measurement  |   Temperature Sensor Manufacturing  |   Temperature Sensors  |   Temperature Transmitters  |   Thermal Imagers  |   Thermistors  |   Thermocouple  |   Thermocouple Wire | Thermowell  |   Ultrasonic Flow Meters  |   Vortex Flow Meter  |   Wireless Sensors