Dual DIN Rail Temperature Transmitter
TXDIN70
PLACE ORDER - Provides Two-Channel Transmitters or Signal Isolators (4 to 20 or 0 to 20 mA)
- Programmable Input Types and Ranges with the Optional External Display (required to program unit- model number is TXDIN70-DISPLAY)
- DIN Rail Mounted
- Inputs are not isolated- Only use UNGROUNDED thermocouple sensors
- Universal Power Supply
- For thermocouples and RTD: Unit displays deg C only
Description
Description
It provides 2 channels ofconfigurable inputs, andsupports multiple voltage, RTD,thermocouple inputs with autoreference junction compensation.If parallel connected to an externalprecise resistance, it acceptscurrent signal input. Each channelhas its own digital filtering and canadjust its filtering degree.- It generates two isolated currentoutputs, 4 to 20 or 0 to 20 mA.The range of retransmissionoutput can be freely defined.
- The model is DIN rail mounted.Its width is only 22.5 mm.The instrument can be easilyconfigured by connecting toour E8 handset display.
- Universal power supply of100 to 240 Vac or 24 Vdc.
SPECIFICATIONS
Input Type
Thermocouple: K, J, T, E, R, S, B, N WRe5-WRe26
RTD: Pt100, Cu50
Linear Voltage: 0 to 20 mV, 0 to60 mV, 0 to 100 mV, 0 to 1V, 0.2 to1V
Instrument Input RangeK(-50 to 1300°C), S(-50 to 1700°C), R(-50 to 1700°C), T(-200 to 350°C), E(0 to 1000°C), J(0 to 1200°C), B(0 to 1800°C), N(-50 to 1300°C), WRe5%WRe26(0 to 2300°C), Pt100(-200 to 900°C)
Linear Input: -9990 to 30,000 units defined by user
Retransmission Accuracy: 0.3% FS ±1 digit (including input and output error)
Output Specification: Can be freely defined in the range of 0 to 22 mA with maximum output voltage ≥11V
Temperature Drift: ≥0.015%FS/°C(including the temperature drift ofinput and output)
Electromagnetic Compatibility (EMC): ±4 KV/5 KHz according toIEC61000-4-4 (EFT); 4 KVaccording to IEC61000-4-5
Isolation Withstanding Voltage:Voltage between power, signal inputand output terminals ≥2300 Vdc;
Power Supply: 100 to 240 Vac, -15%,+10% /50 to 60 Hz; or 24VDC
Power Consumption: ≥3W
Operating Ambient: Temperature-10 to 60°C; humidity ≥90%RH
Note: B thermocouple obtains the abovemeasurement accuracy only at the range of400 to 1800°C. It's measurement from 60 to400°C is less accurate. Anemometer | Automation | Accelerometers | Calibrator | Cartridge Heaters | Chart Recorders | Cryogenics | Custom Pressure Transducers | Data Loggers | Data Acquisition | Dial Thermometers | Fiber Optics | Fiber Optic Temperature Measurement | Flexible Heaters | Flow Meters | Glass Bulb Thermometers | Grippers | Heaters | Humidity Measurement | Integrated Circuit Sensors | Immersion Heaters | Infrared Thermometers | Level Measurement | Load Cells | M12 Temperature Connectors | Magnetic Flow Meter | Panel Meter | PID Controllers | pH meter | Pressure Gauges | Pressure Transducers | Pressure Transmitters | Rotameters | RTD | Remote Process Monitoring | Sanitary Sensors | Signal Conditioners | Stepper Motors | Strain Gages | Strip Heaters | Temperature Controllers | Temperature Labels | Temperature Measurement | Temperature Sensor Manufacturing | Temperature Sensors | Temperature Transmitters | Thermal Imagers | Thermistors | Thermocouple | Thermocouple Wire | Thermowell | Ultrasonic Flow Meters | Vortex Flow Meter | Wireless Sensors