Temperature Transmitter for Thermocouples- RTD's- Millivolt input and Resistance
TX86
PLACE ORDER - Universal Input RTD, T/C, Ω, POT and mV
- Models for 100, 200, 500, 1000 Ω, 0.00385 2- or 3-Wire RTD’s
- Field Scalable
- Programming by Push-Buttons on Front
- Isolation 1000 VRMS Between Input and Output
- Self-Diagnostic With Temp Drift Compensation
- LED Display - High Brightness
- Sensor O/C and S/C Detection
- Solid State Relay Output
Description
Description
The TX86 is a 2-wire Loop-Powered,Galvanic-Isolated, ProgrammableUniversal Input TemperatureTransmitter that is designed to behead-mounted, but can bestandalone as well. It uses 16 bitsA/D and D/A converters offering highaccuracy with Linearized 4 to 20 mAor 20 to 4 mA outputs. Being a user-friendlyrugged instrument, itdisplays the measured variable andhas a SSR output.The TX86 has 3 push buttons on itsfront keyboard & a 4-digit 7-segmentbright LED display module thatindicates the values of the measuredparameters during the MeasuringMode while also providing promptingand programming instructions duringthe setup and calibration moderoutines.The 1000V AC galvanic isolationremoves all ground loop effects.Three different engineering units(°C, °F and %), can be displayedand the chosen unit is highlightedby an associated LED lamp when inthe measuring mode.
SPECIFICATIONS Input Sensors | Measured Range (°C) | Minimum Span (°C) |
---|
K | -100 to 1372 | 50 |
J | -100 to 750 | 50 |
T | -100 to 400 | 50 |
E | -100 to 750 | 50 |
R | 0 to 1700 | 50 |
N | -100 to 1300 | 50 |
S | 0 to 1700 | 50 |
B | 400 to 1800 | 50 |
100PT | -200 to 850 | 50 |
200PT | -200 to 500 | 50 |
500PT | -200 to 200 | 25 |
1000PT | -200 to 200 | 25 |
Ni120 | -80 to 260 | 50 |
Cu10 | -100 to 260 | 50 |
Resistance | 0 to 2000Ω | 50Ω |
Potentiometer | 0 to 2000Ω | 50Ω |
mV (millivolts) | -5 to +60 | 2 mV |
General Performance: (@ 24 Vdc, 25°C ±2°C)
Loop Power: 12 to 30 Vdc, LED indicator reverse polarity protected 60 Vdc
Output: 4/20 mA calibrated; 3.8 to 20.5 mA linear
Resolution: 2uA
RTD Excitation Current: 30/150 uA ± 2%
Input Impedance: 1 MΩ, nominal
Maximum Load: 50 x (Vsupply – 12V) Ω
Accuracy: ± 0.2% of full scale input
Long-Term Stability: ± 0.15%/ year
Temp. Coefficient: ± 0.01%/°C (5 to 50°C)
Dampening Constant: Programmable
Configuration: Via 3 push-buttons on front
Solid State Relay Output: 30 mA maximum
Cold Junction Comp: ± 2°C max (5 to 50°C)
Power Supply Effect: Less than 0.01%/V
Input Protection: 40 Vdc maximum
Sensor Burnout: Upscale >21mA, downscale <3.8 mA
Isolation Rating: 1000V RMS continuous
Response Time: 1 second with dampening off
Power-on Response: Within 5 seconds
Ambient Temps: -20 to 70°C (-4 to 158°F) (storage and operation)
Relative Humidity: 20 to 90%, non-condensing
Dimensions: 62 Dia x 42 mm H (2.5 x 1.7")
Mounting: Head-mounted
Housing: Plastic, polycarbonate
Weight: 80 g (0.18 lb) Anemometer | Automation | Accelerometers | Calibrator | Cartridge Heaters | Chart Recorders | Cryogenics | Custom Pressure Transducers | Data Loggers | Data Acquisition | Dial Thermometers | Fiber Optics | Fiber Optic Temperature Measurement | Flexible Heaters | Flow Meters | Glass Bulb Thermometers | Grippers | Heaters | Humidity Measurement | Integrated Circuit Sensors | Immersion Heaters | Infrared Thermometers | Level Measurement | Load Cells | M12 Temperature Connectors | Magnetic Flow Meter | Panel Meter | PID Controllers | pH meter | Pressure Gauges | Pressure Transducers | Pressure Transmitters | Rotameters | RTD | Remote Process Monitoring | Sanitary Sensors | Signal Conditioners | Stepper Motors | Strain Gages | Strip Heaters | Temperature Controllers | Temperature Labels | Temperature Measurement | Temperature Sensor Manufacturing | Temperature Sensors | Temperature Transmitters | Thermal Imagers | Thermistors | Thermocouple | Thermocouple Wire | Thermowell | Ultrasonic Flow Meters | Vortex Flow Meter | Wireless Sensors