  • ±0.03% Accuracy (Typical)
  • ±0.01% Linearity
  • 1500Vrms Transformer Isolation and 240Vrms Field-Side Protection
  • ANSI/IEEE C37.90.1 Transient Protection
  • Wide Loop Supply Voltage, 10.8V to 60V
  • 5-Pole Low-Pass Filtering
  • Up to 160 dB CMR
  • 85dB NMR at 60Hz, 80dB at 50Hz
  • Protected Against Reverse Connection of Loop Voltage
  • -40 to 80°C (-40 to 176°F) Operating Temperature
  • Mounts on DIN Rail EN 50022, 35 x 7.5 or 35 x 15
  • CE Compliant
  • Manufactured per RoHS Directive 2002/95/EC
 Manuals (contact with email : [email protected])
 Print
Description

Description

The new DRLP Series of loop powered 2-wiretransmitters consists of seven family groups with atotal of 48 transmitter models that interface to a widevariety of voltage, current, temperature and positionmeasuring devices. The DRLP Series providessuperior specifications such as ±0.03% accuracy, fivepoles of filtering, 1500 Vrms continuous isolation, lowoutput noise, and much more.The DRLP Series 2-wire transmitter conditions andsends analog signals from sensors located in the“field” to monitoring and control equipment, usuallycomputers, located thousands of feet away in centralcontrol areas. The DRLP Series accepts a widerange of inputs, including millivolt, volt, milliamp,thermocouple, RTD, potentiometer, and slide wire.It operates on power from a 2-wire signal loop andmodulates the supply current to represent the inputsignal within a 4 to 20-milliamp range.Two-wire transmission loops are very economicalmethods for connecting sensors to distant controlrooms. Since the DRLP Series operates from thesignal loop current, no additional, expensive powerand wiring are required. Only low cost, twisted pairwiring is needed.

DRLP Loop Drive Capability
The DRLP Series transmitter’s wide range of loopsupply voltage (10.8V to 60V) makes it a versatiledevice which can be used in most any current loop. Themaximum loop resistance is determined by subtractingthe transmitter’s minimum loop supply voltage from thetotal loop supply voltage and dividing the result by themaximum loop current (see graph).The low loop supply voltage of 10.8V allows the DRLPto be used in applications with low output powersupplies and the high Loop Supply Voltage of 60V allowsuse in applications with long distance current loops.

COMMON SPECIFICATIONS
Input Protection
  Continuous: 240 Vrms maximum
  Transient: ANSI/IEEE C37.90.1
CMV, Input to Output
  Continuous: 1500 Vrms maximum
  Transient: ANSI/IEEE C37.90.1
Noise
  Output: 100 kHz:3µArms
Output Range: 4 to 20 mA
Output Protection
  Reverse Polarity: Continuous
  Over-Voltage: 240 Vrms continuous
  Transient: ANSI/IEEE C37.90.1
Loop Supply Voltage: 10.8V to 60V
Loop Supply Sensitivity: ±0.0005%/V
Turn-On Delay: 400 ms
Environmental
  Operating Temperature Range: -40 to 80°C (-40 to 176°F)
  Storage Temperature Range: -40 to 80°C (-40 to 176°F)
Relative Humidity: 0 to 95% non-condensing
Emissions EN61000-6-4: ISM, Group 1
  Radiated, Conducted: Class A
Immunity EN61000-6-2: ISM, Group 1
  RF: Performance A ±0.5% span error
  ESD, EFT: Performance B
Mechanical Dimensions: 75 H x 22.5 W x 105 mm D(2.95 x 0.89 x 4.13")
Mounting: DIN EN 50022 35 x 7.5 mm or35 x 15 mm rail

See attached PDF for detailed Transmitter Specifications
Anemometer  |   Automation  |   Accelerometers  |   Calibrator  |   Cartridge Heaters  |   Chart Recorders  |   Cryogenics  |   Custom Pressure Transducers  |   Data Loggers  |   Data Acquisition  |   Dial Thermometers  |   Fiber Optics  |   Fiber Optic Temperature Measurement  |   Flexible Heaters  |   Flow Meters  |   Glass Bulb Thermometers  |   Grippers  |   Heaters  |   Humidity Measurement  |   Integrated Circuit Sensors  |   Immersion Heaters  |   Infrared Thermometers  |   Level Measurement  |   Load Cells  |   M12 Temperature Connectors  |   Magnetic Flow Meter  |   Panel Meter  |   PID Controllers  |   pH meter  |   Pressure Gauges  |   Pressure Transducers  |   Pressure Transmitters  |   Rotameters  |   RTD  |   Remote Process Monitoring  |   Sanitary Sensors  |   Signal Conditioners  |   Stepper Motors  |   Strain Gages   |   Strip Heaters  |   Temperature Controllers  |   Temperature Labels  |   Temperature Measurement  |   Temperature Sensor Manufacturing  |   Temperature Sensors  |   Temperature Transmitters  |   Thermal Imagers  |   Thermistors  |   Thermocouple  |   Thermocouple Wire | Thermowell  |   Ultrasonic Flow Meters  |   Vortex Flow Meter  |   Wireless Sensors