DIN Rail 2-Wire Transmitter Isolators
DRSL-LPO_Series
PLACE ORDER - 1 Channel (DRSL-LPO-1) or 2 Channel (DRSL-LPO-2) 2-Wire Transmitter Isolators
- Powered By the Host (Output) Current Signal Loop
- 1:1 Signal Ratio
- Low Channel Voltage Drop
- Available Input Transmitter (Tx) Supply
- Fast Response Time <5 ms
- High Conversion Accuracy, <0.05% of Span (3.8 to 20.5 mA)
- Slimline 6 mm (0.24") Housing
Description
Description
The DRSL-LPO Series DIN rail2-wire transmitter isolators provide acompetitive choice in terms of bothprice and technology for galvanicisolation of current signals toSCADA systems or PLC equipment.These units provide isolation and1:1 conversion of standard currentsignals and are powered by the host(output) current signal loop. Inputtransmitter (Tx) power supply of3.5 to 32.5V is provided.
The DRSL-LPO series offers isolationbetween input and output, providessurge suppression and protectscontrol systems from transients andnoise. These units also eliminateground loops and can be used formeasuring floating signals. Lowpower consumption facilitates DIN railmounting without the need for any airgap. Measurement ranges are factorycalibrated. These isolators operatesover a wide temperature range from-25 to 70°C (-13 to 158°F).
SPECIFICATIONS
NUMBER OF CHANNELS
DRSL-LPO-1: 1
DRSL-LPO-2: 2
CURRENT INPUT
Signal Range (Input to Output): 3.8 to 20.5 mA
Signal Conversion: 1:1
Functional Range: 3.5 to 23 mA (NAMUR NE43 compliant)
Available 2-Wire Transmitter (Tx) Supply: 3.5 to 32.5V
CURRENT OUTPUT
Output Loop Current Limitation: 24 mA typical
Output Overload: 50 mA max
GENERAL
Supply Voltage: 6 to 35 Vdc
Internal Consumption: 50 mW per channel
Voltage Drop (Input to Output): 2.5V typical
Isolation Voltage (Test): 2.5 kVac
Isolation Voltage (Working): 300 Vac
Signal/Noise Ratio: >60 dB
Cut-Off Frequency (3 dB): 100 Hz
Response Time (0 to 90%, 100 to 10%): <5 ms
Absolute Accuracy (at 25°C): ≤±8 µA
Temperature Coefficient (>25°C): ≤±0.02 µA [(T-25°C) x Vsupply]
Temperature Coefficient (<25°C): ≤±0.07 µA [(T-25°C) x Vsupply]
EMC Immunity Influence: <±0.5% of span (4 to 20 mA)
Extended EMC Immunity NAMUR NE 21, A Criterion, Burst: <±1% of span
ENVIRONMENTAL
Operating Temperature: -25 to 70°C (-13 to 158°F)
Storage Temperature: -40 to 85°C (-40 to 185°F)
Calibration Temperature: 20 to 28°C (68 to 82°F)
Relative Humidity: 0 to 95% RH non-condensing
Protection Degree: IP20
Installation Area: Pollution degree 2 and measurement/overvoltage category II
MECHANICAL
Dimensions: 113 H x 6.1 W x 115 mm D (4.4 x 0.24 x 4.5")
Weight: 70 g (0.15 lb) approx
DIN Rail Type: DIN EN 60715 - 35 mm
Wire Size: 0.13 x 2.5 mm²/ AWG 26 to 12 stranded wire
Screw Terminal Torque: 0.5 Nm Anemometer | Automation | Accelerometers | Calibrator | Cartridge Heaters | Chart Recorders | Cryogenics | Custom Pressure Transducers | Data Loggers | Data Acquisition | Dial Thermometers | Fiber Optics | Fiber Optic Temperature Measurement | Flexible Heaters | Flow Meters | Glass Bulb Thermometers | Grippers | Heaters | Humidity Measurement | Integrated Circuit Sensors | Immersion Heaters | Infrared Thermometers | Level Measurement | Load Cells | M12 Temperature Connectors | Magnetic Flow Meter | Panel Meter | PID Controllers | pH meter | Pressure Gauges | Pressure Transducers | Pressure Transmitters | Rotameters | RTD | Remote Process Monitoring | Sanitary Sensors | Signal Conditioners | Stepper Motors | Strain Gages | Strip Heaters | Temperature Controllers | Temperature Labels | Temperature Measurement | Temperature Sensor Manufacturing | Temperature Sensors | Temperature Transmitters | Thermal Imagers | Thermistors | Thermocouple | Thermocouple Wire | Thermowell | Ultrasonic Flow Meters | Vortex Flow Meter | Wireless Sensors