Your Source for Process Measurement & Control
UK
44-796-072-6366
Germany
49-178-631-1266
Modbus® Serial Interface Modules
D6000 Series
PLACE ORDER - Complete Data Acquisition Systems
- Analog and Digital I/O Models Available
- RS485 Serial Communications Interface
- MODBUS® RTU Protocol
- Up to 25 Conversions per Second
- 500 Vrms Analog Input or Analog Output Isolation
- 16-Bit Analog Input Measurement Resolution
- Continuous Self-Calibration; No Adjustments Required
- Programmable Analog Input Digital Filters
- Requires 10V to 30 Vdc Unregulated Supply
- Transient Suppression on Serial RS485 Data Lines
- Removable Screw Terminal Plug Connectors Supplied
- Process Monitoring and Control
- Remote Data Logging to any Host Computer
- Product Testing
- Direct Connection to PLC
Description
Description
The D6000 Series modules are a family of completedata acquisition modules for use in process controlsystems. The analog input models can measureprocess signals such as thermocouples, 4 to 20 mAloops, and discrete contact closures. The analogoutput models can generate voltage or current signalsfor controlling annunciators or valves. The digital inputand output models can sense the state of remotedigital signals or control solid state relays. Completedata acquisition systems can be created with easewith the D6000 modules and a host supervisorycomputer or programmable logic controller.The modules provide direct connection to a widevariety of sensors and annunciators. They performall signal conditioning and linearization and containno pots or DIP switches. All user-selectable settings,such as ranges, communications settings are storedin nonvolatile EEPROM, which maintains these valueseven after power is removed.The D6000 series modules communicate with ahost computer using the MODBUS RTU protocol.The MODBUS RTU protocol is widely recognizedthroughout the data acquisition industry by andsupported by almost all commercially availableprocess control programs and supervisory host PLC’s.
This binary protocol communicates via a two-wireRS485 serial interface. The key to the product conceptis that the modules are easy to connect and use. Youdo not need engineering experience in complicateddata acquisition hardware. With the modules, anyonefamiliar with a personal computer can construct a dataacquisition system.This modular approach to data acquisition is veryflexible, easy to use and cost effective. The modules canbe mixed and matched to fit your application. They canbe placed remote from the host and from each other.The D6000 series is completely hardware compatiblewith the D1000M, D1700M, D3000M and D5000M seriesmodules. Meaning, they can all be mixed and matchedon one RS485 serial communications line. Each moduleis identified by a unique user-programmable address.This addressing technique allows modules to beinterrogated in any order.
ANALOG INPUT MODULES
The D6100 through D6400 Series analog input modulescontain seven input channels and make up a completedata acquisition system. Each unit contains analogsignal conditioning circuits optimized for a specific inputtype. The amplified sensor signals are converted todigital data with a microprocessor-controlled integratingA/D converter. Offset and gain errors in the analogcircuitry are continuously monitored and corrected usingmicroprocessor techniques.The analog input modules output the resultant digitaldata as unsigned integer percentage of full-scale valuesthat are compatible with the MODBUS RTU protocol.The modules continuously convert data at the rate ofup to 25 conversions per second and store the latestresult in a buffer. Host processors may request data bysending a MODBUS query to the module. The D6000series modules will instantly respond by communicatingthe memory buffer data back to the host processor. Upto 247 modules may be linked to a single RS485 port.
ANALOG OUTPUT MODULES
The D6500 analog output modules contain two 12-bitdigital to analog converters (DAC) for generating eithervoltage or current output signals. The output signaltype for each DAC is user selectable and each DAC isindependently controlled via a host computer using theMODBUS RTU protocol. Two voltage and two currentranges are available.The D6500 analog output modules also containprogrammable features such as output slew rate,a communications watchdog timer, programmablestartup signal value, and an 8-bit analog to digitalconverter for analog readback the output signal. Thecommunications watchdog timer can be used to movethe analog output signal to a known “safe” condition inthe event of a communications failure.
DIGITAL INPUT MODULES
The D6710 digital input modules contain 15 individualsignal inputs for monitoring logic levels, contactclosures, or other ON/OFF signals in a data acquisitionsystem. Each discrete input terminal contains a pullupbiasing resistor allowing for direct connection to aset of contacts. The input terminals can accept signalsbetween ±30 Vdc without damage.
DIGITAL OUTPUT MODULESThe D6720 digital output modules contain 15 individualopen-collector transistor outputs for controllingannunciators, lamps, or other devices that require anON/OFF signal.The D6720 digital output modules also containprogrammable features such as a communicationswatchdog timer and programmable startup signalvalues for each bit.The communications watchdog timer can be usedto move the digital output signals to a known “safe”condition in the event of a communications failure.
COMMUNICATIONS
The D6000 series modules are designed toeasily interface with computers and PLC’s. Allcommunications to and from the module areperformed using the Modbus RTU protocol via anRS485 interface.The two-wire RS485 system is a half duplex system,developed for multi-dropped systems that cancommunicate at high data rates over long distances.RS485 receivers can handle common mode voltagesfrom -7 to 12V without loss of data, making them idealfor transmission over great distances.
MODBUS® COMMAND SET
The D6000 series modules use the Modbus RTUprotocol for communications. The Modbus RTUbinary protocol uses a master-slave technique, inwhich only the master device can initiate transactions.The slave devices respond by supplying the requesteddata to the master or by performing the requestedaction in the query. The master can address anyslave device. The returned messages are consideredresponse messages. The supported master functioncodes are:
Modbus RTU Functions and Descriptions
01 – Read Coil Status
02 – Read Register Status
03 – Read Holding Registers
04 – Read Input Register (Analog Inputs)
05 – Force Single Coil
06 – Preset Single Register
0F – Force Multiple Coils
10 – Preset Multiple Registers
PROCESS CONTROL SOFTWARE
Modbus RTU protocol is one of the most widelysupported serial protocols in the data acquisitionmarket. Modbus RTU software drivers are availablefor almost every data acquisition software programavailable today. Thus providing instant connectivitybetween the D6000 modules and most dataacquisition software programs.
SETUP
The D6000 series are initiated at the factory usingthe Modbus RTU protocol. Features such as theModbus device address, baud rate, and analogsignal ranges can be easily configured using thesetup software. Each D6000 module must be properlyconfigured before installation into a Modbus system.
UTILITY SOFTWARE
Complimentary Utility Software is included with eachpurchase order. The software is compatible withWindows® operating systems and distributed onCD-ROM. The Utility Software simplifies configurationof all user selectable options such as device address,baud rate and filtering constants. The latest versionof our software is always available on our web site attrodeks.com.
SPECIFICATIONS
D6000
(Typical @ 25°C and nominal power supplyunless otherwise noted)
GENERAL
Programmable Digital Filters: In analog input modules
Maximum CMV (Input to Output at 115Vrms, 60Hz):500V rms
Setups: Stored in EEPROM
Unused Analog Input Channels: Software disable
INTERFACE
Communications: Modbus RTU protocol/RS485 Serial port
SERIAL COMMUNICATIONS
Baud Rates: 9600, 19.2K, 38.4K, 57.6K, 115.2K
Data Format: 8 data bits, and 1 or 2 stop bits
Parity: Odd, even, none
Channel Address: User selectable
Number of Modules: Up to 247 multi-drop modules perhost serial port
Communications Distance: Up to 1219 m (4000') (RS485)
Transient Suppression: On RS485 data lines
POWER REQUIREMENTS
Unregulated 10V to 30 Vdc, protected against powersupply reversals
ENVIRONMENTAL
Operating Temperature Range:-25 to 70°C (-13 to 158°F)
Storage: -25 to 85°C (-13 to 185°F)
Relative Humidity: 0 to 95% non-condensing
PACKAGE, DIMENSIONS AND CONNECTORS
Case: ABS thermoplastic, UL-94-5VA rated
Dimensions:102 H x 152 W x 38 mm D (4 x 6 x 1.5");
mounting holes165 mm (6.6") on center
Connectors: Screw terminal barrier plug (supplied)
MODULE SPECIFICATIONS
D6100 Voltage Inputs
Number of Channels: 7 differential voltage inputs
Ranges: ±0.025V, ±0.05V, ±0.1V, ±1V, ±5V, ±10V
Resolution ADC: 16-bit ADC, 25/20 conversions per second
Accuracy: ±0.05% of FS maximum
Span Tempco: ±50ppm/°C maximum
Input Burnout Protection: To 250 Vac
Input impedance: 20 MΩ min
Power Requirements: Serial = 1.4W
D6200 CURRENT INPUTS
Number of Channels: 7 differential current inputs
Range: ±20 mA
Resolution ADC: 16-bit ADC, 25/20 conversions per second
Accuracy: ±0.05% of FS maximum
Span Tempco: ±50ppm/°C maximum
Voltage Drop: 2.0V maximum
Input impedance: <100 Ω (70 typical)
Power Requirements: Serial = 1.4W
D6300 THERMOCOUPLE IPUTS
Number of Channels: 7 differential thermocouple inputs
Thermocouple Types: J, K, T, E, R, S, B, and C
Ranges:
J = -200 to 760°C (-328 to 1400ºF)
K = -150 to 1250°C (-238 to 2282ºF)
T = -200 to 400°C (-328 to 752ºF)
E = -100 to 1000°C (-148 to 1832ºF)
R = 0 to 1750°C (32 to 3182ºF)
S = 0 to 1750°C (32 to 3182ºF)
B = 0 to 1820°C (32 to 3308ºF)
C = 0 to 2315°C (32 to 4199ºF)
Thermocouple Accuracy
(Error From all Sources) from 0 to 40°C Ambient:
J, K, T, E = ±1.5°C maximum;R, S, B, C = ±3.5°C maximum; (300°C to +F.S.)
Resolution ADC: 16-bit ADC, 25/20 conversions per second
Input Impedance: 20 MΩ min
Cold Junction Compensation: Automatic
Lead Resistance Effect: <40 µV per 350 Ω
Indication: Open thermocouple and over range indication
Input Burnout Protection: To 250 Vac
Power Requirements: Serial = 1.4W
D6400 VOLTAGE, THERMOCOUPLE, CURRENT INPUTS
Number of Channels: 7 differential voltage,thermocouple, current inputs
Specifications: Equal to D6100, D6200 and D6300 series
D6500 ANALOG OUTPUTS
Number of Channels: Two analog outputs(programmable for voltage or currrent output)
Voltage Range: 0 to 10 Vdc, ±10 Vdc
Current Ranges: 0 to 20 mA, 4 to 20 mA
Update Rate: 250 conversions per second
Accuracy: ±0.1%
DAC Resolution: 12-bit
Span Tempco: ±25ppm/°C maximum
Settling Time to 0.1% FS: 1 mS
Communications: Watchdog timer
Current Output Compliance: ±12 Vdc
Voltage Output Drive: 5 mA maximum
ADC Analog Output Signal Readback: 8-bit
Isolation: 500 Vac, output common to system ground
Current Output Burnout: Protected to 250 Vac
Power Requirements: Serial = 2.1W
D6710 DIGITAL INPUTS
Number of Channels: 15 digital inputs
Internal: 10K pull-up resistors on each bit acceptdirect switch closure
Logic “0”: <1Vdc, Logic “1”: = >3.5Vdc
Input Burnout: To ±30 Vdc without damage
Isolation: 500 Vac, input common to system ground
Power Requirements: Serial = 0.75W
D6720 DIGITAL OUTPUTS
Number of Channels: 15 Open-collector outputs to30 Vdc, 100 mA maximum
Vsat: +0.3 Vdc maximum at 100 mA
Short Circuit Protection: To 500 mA
Communications: Watchdog timer
Digital Output Update Rate: 4.5 Hz
Isolation: 500 Vac, output common to system ground
Power Requirements: Serial = 1.0W Anemometer | Automation | Accelerometers | Calibrator | Cartridge Heaters | Chart Recorders | Cryogenics | Custom Pressure Transducers | Data Loggers | Data Acquisition | Dial Thermometers | Fiber Optics | Fiber Optic Temperature Measurement | Flexible Heaters | Flow Meters | Glass Bulb Thermometers | Grippers | Heaters | Humidity Measurement | Integrated Circuit Sensors | Immersion Heaters | Infrared Thermometers | Level Measurement | Load Cells | M12 Temperature Connectors | Magnetic Flow Meter | Panel Meter | PID Controllers | pH meter | Pressure Gauges | Pressure Transducers | Pressure Transmitters | Rotameters | RTD | Remote Process Monitoring | Sanitary Sensors | Signal Conditioners | Stepper Motors | Strain Gages | Strip Heaters | Temperature Controllers | Temperature Labels | Temperature Measurement | Temperature Sensor Manufacturing | Temperature Sensors | Temperature Transmitters | Thermal Imagers | Thermistors | Thermocouple | Thermocouple Wire | Thermowell | Ultrasonic Flow Meters | Vortex Flow Meter | Wireless Sensors