Your Source for Process Measurement & Control
UK
44-796-072-6366
Germany
49-178-631-1266
Product Groups
4-Channel Current Output Card for OMB-DAQBOARD-2000 Series
TRODEKS Engineering | Thermocouples, Pressure Transducers, Flow Meters, PID Controllers
OMB-DBK5
PLACE ORDER 
  • Provides Four Isolated 4 to 20 mACurrent Outputs
  • Compatible With 12 To 45V Current Loop Supplies
  • Features PredictablePower-On & Fault States
  • Provides 12-Bit Resolution
 Manuals (contact with email : [email protected])
 Print
Description

Description

The OMB-DBK5 current-outputcard provides OMB-DAQBOARD-2000Series data acquisitionsystems with the ability to controlfour isolated 4 to 20 mA currentloops. The OMB-DBK5 acts as acurrent loop transmitter bymodulating current from an externalsource. The OMB-DBK5 can beprogrammed with a static valuewhenever the data acquisitionsystem is not transferring A/D data.As many as sixty-four OMB-DBK5’scan be used in one system, toobtain up to 256 outputs.

Architecture
Each of the OMB-DBK5’s channelscontains a 12-bit D/A converter toset the loop current. All channelsare optically isolated from the dataacquisition system and from oneanother by 500 V.

Current Loop
The OMB-DBK5 is compatible withregulated or unregulated loopsupplies of 12 to 45 Vdc. It alsoprovides compliance with loopresistances of up to 1950 ohms,depending on the source magnitude.

Current Loop-Powered Outputs
Since the isolated outputs of theOMB-DBK5 are loop powered, thecard maintains control of the loopcurrent even when the dataacquisition system is powered down.When loop power is first applied, theOMB-DBK5’s outputs assume their4 mA default state. If at any time thedata acquisition system’s power islost or communication with the dataacquisition system fails, theOMB-DBK5’s outputs retain theirlast set values.

Specifications
Connectors:

DB37 male, mates with P1pinout on OMB-DAQBOARD-2000Series; screw terminals for signaloutputs
Accuracy/Linearity:0.1% full scale
Resolution:4 µA/LSB, monotonic
Isolation: 500 V
Voltage Range:V loop = 12 to 45 V
Compliance: R loop = (V loop - 6) / 0.020
Example Voltage
@ Vexc = 35 V; MDR* = 1450 Ohms
@ Vexc = 15 V; MDR* = 450 Ohms
* MDR (maximum drive resistance)
Cables: Use OMB-CA-37-x withOMB-DAQBOARD-2000 Series
Anemometer  |   Automation  |   Accelerometers  |   Calibrator  |   Cartridge Heaters  |   Chart Recorders  |   Cryogenics  |   Custom Pressure Transducers  |   Data Loggers  |   Data Acquisition  |   Dial Thermometers  |   Fiber Optics  |   Fiber Optic Temperature Measurement  |   Flexible Heaters  |   Flow Meters  |   Glass Bulb Thermometers  |   Grippers  |   Heaters  |   Humidity Measurement  |   Integrated Circuit Sensors  |   Immersion Heaters  |   Infrared Thermometers  |   Level Measurement  |   Load Cells  |   M12 Temperature Connectors  |   Magnetic Flow Meter  |   Panel Meter  |   PID Controllers  |   pH meter  |   Pressure Gauges  |   Pressure Transducers  |   Pressure Transmitters  |   Rotameters  |   RTD  |   Remote Process Monitoring  |   Sanitary Sensors  |   Signal Conditioners  |   Stepper Motors  |   Strain Gages   |   Strip Heaters  |   Temperature Controllers  |   Temperature Labels  |   Temperature Measurement  |   Temperature Sensor Manufacturing  |   Temperature Sensors  |   Temperature Transmitters  |   Thermal Imagers  |   Thermistors  |   Thermocouple  |   Thermocouple Wire | Thermowell  |   Ultrasonic Flow Meters  |   Vortex Flow Meter  |   Wireless Sensors