Your Source for Process Measurement & Control
UK
44-796-072-6366
Germany
49-178-631-1266
Product Groups
Passive Loop Powered Isolator
TRODEKS Engineering | Thermocouples, Pressure Transducers, Flow Meters, PID Controllers
DR910
PLACE ORDER 
  • Loop Powered
  • Isolated
  • 0 to 20 mA, 4 to 20 mA Ranges
  • Din Rail Mountable
 Manuals (contact with email : [email protected])
 Print
Description

Description

The DR910 passive isolator is used for the electrical isolation andprocessing of analog 0 to 20 mA or 4 to 20 mA standard current signals.The DR910 provides electrical isolation between the controlelectronics and process I/O. In addition, interference signals above75 Hz are effectively suppressed. Input and output circuit do notrequire separate auxiliary power.

The DR910 obtains power from the input signal. The modules aresnapped onto symmetrical DIN rails in accordance with EN 50 022.When using the DR910, ensure that the current-driving voltage of themeasuring transducer is sufficient for driving the maximum current of20 mA, with a power loss of 2.5 V (2.5 V + (20 mA * RLOAD). Voltage drop across the input iscalculated by determining the load resistance of the output loop,drawing a vertical line to the curve (see diagram), then horizontally tothe voltage drop.

The energy for the supply on the input side is taken from the analoginput signal. Due to the dynamic input resistance, a power loss ofapproximately 2.5 V drops at the module input.

SPECIFICATIONS
Input Range:
0 to 20 mA, 4 to 20 mA
Maximum Input Current/Voltage: 50 mA/30 Vdc
Input Resistance@ 20 mA: 125 to 1125 Ω (dependent on load)
Voltage Drop at Input: See Chart on PDF
Maximum Input Frequency: <75 Hz
Response Time: 5 msec max
Output Signal: 0 to 20 mA, 4 to 20 mA
Max Load Resistance: <1375 Ω @ 20 mA
Isolation Voltage: 510 V, 50 Hz, for 1 minute
Accuracy: <0.1% of full scale
Operating Temperature: -10 to 70°C (14 to 158°F)
Temperature Coeficient: <0.002%/K of the measured value
Enclosure: Case body is green, Polyamide PA
Mounting: Standard DIN style rail, including top hat (T) profile railaccording to EN50022 - 35 X 7.5 and 35 X 15, and G profile railaccording to EN50035 - G32.
Weight: 84.4 g (3 oz)
Anemometer  |   Automation  |   Accelerometers  |   Calibrator  |   Cartridge Heaters  |   Chart Recorders  |   Cryogenics  |   Custom Pressure Transducers  |   Data Loggers  |   Data Acquisition  |   Dial Thermometers  |   Fiber Optics  |   Fiber Optic Temperature Measurement  |   Flexible Heaters  |   Flow Meters  |   Glass Bulb Thermometers  |   Grippers  |   Heaters  |   Humidity Measurement  |   Integrated Circuit Sensors  |   Immersion Heaters  |   Infrared Thermometers  |   Level Measurement  |   Load Cells  |   M12 Temperature Connectors  |   Magnetic Flow Meter  |   Panel Meter  |   PID Controllers  |   pH meter  |   Pressure Gauges  |   Pressure Transducers  |   Pressure Transmitters  |   Rotameters  |   RTD  |   Remote Process Monitoring  |   Sanitary Sensors  |   Signal Conditioners  |   Stepper Motors  |   Strain Gages   |   Strip Heaters  |   Temperature Controllers  |   Temperature Labels  |   Temperature Measurement  |   Temperature Sensor Manufacturing  |   Temperature Sensors  |   Temperature Transmitters  |   Thermal Imagers  |   Thermistors  |   Thermocouple  |   Thermocouple Wire | Thermowell  |   Ultrasonic Flow Meters  |   Vortex Flow Meter  |   Wireless Sensors