Your Source for Process Measurement & Control
UK
44-796-072-6366
Germany
49-178-631-1266
Low Profile DIN Rail Power Supplies for industrial devices
LP-PS Series Power Supplies
PLACE ORDER - 15 to 100 Watts for 5, 12 & 24 VDC
- Universal AC Inputs/Full Range
- Fits in 4" Deep Enclosures
- Isolation Class 2
- Protections: Short Circuit/ Overload/Overvoltage
- LED Indicator for Power On
- % Full Load Burn-In Test
- Install on 35 x 7.5 or 35 x 15 mm DIN Rail
Description
Description
The LP-PS Series of power suppliesprovides a reliable DC power source for anyindustrial control system. These economicaland reliable power supplies for industrialdevices are designed to take minimal depthin your electrical control cabinet. The LP-PSSeries power supplies offering short-circuit,over-load and over-voltage protection. Thesehigh quality power supplies have passed a100% full load burn-in test, and are ULlisted, CE marked and are class 2 compliant.
SPECIFICATIONS
Working Temperature: -20 to 50°C (-4 to 122°F)
Working Humidity: 20 to 90% RH non-condensing
Dimensions: 96 H x 56 mm D (3.66 x 2.22") for width see "To Order" table
Output Voltage: 24 Vdc
Voltage Tolerance: ±1%
Line and Load Regulation: ±1%
Input Voltage: 85 to 264 Vac, 47 to 63 Hz, 120 to 370 Vdc
AC Current:
LP-PS-1524 and LP-PS-3024: 0.88A/115 Vac, 0.48A/230 Vac
LP-PS-4524: 1.5A/115 Vac, 0.75A/230 Vac
LP-PS-6024: 1.2A/115 Vac, 0.80A/230 Vac
LP-PS-10024: 3A/115 Vac, 1.6A/230 Vac
Inrush Current:
LP-PS-1524: Cold start 35A/115 Vac, 65A/230 Vac
LP-PS-3024: Cold start 15A/115 Vac, 30A/230 Vac
LP-PS-4524: Cold start 30A/115 Vac, 60A/230 Vac
LP-PS-6024: Cold start 18A/115 Vac, 36A/230 Vac
LP-PS-10024: Cold start 30A/115 Vac, 45A/230 Vac
OUTPUT
Ripple and Noise:
LP-PS-1524, LP-PS-3024,
LP-PS-6024 and LP-PS-10024: 150 mVp-p
LP-PS-4524: 480 mVp-p
Voltage Range:
LP-PS-1524, LP-PS-3024,
LP-PS-4524 and LP-PS-6024: 21.6 to 26.4V
LP-PS-100724: 24 to 29V
Protection Overload:
LP-PS-1524, LP-PS-3024,
LP-PS-4524 and LP-PS-6024: 105 to 160%, 27.6 to 32.4V
LP-PS-10024: 105 to 135%, 30 to 35V
Efficiency: 80 to 89%
Safety Standards: EN60950-1, LP-PS-4524 UL508
Withstand Voltage (I/P-O/P): 3k Vac
Insulation Resistance: I/P-O/P, 100 m Ω/500 Vdc EMI compliance to EN55011, EN55022 (CISPR22), Class B
Harmonic Current: Compliance to EN61000-3-2,-3
EMS Immunity 10 and 20 W Models: Compliance to EN61000-4-2, 3, 4, 5, 6, 8, 11, EN50204, EN55024, EN61000-6-1, EN61204-3, light industry level, criteria A
EMS Immunity 40, 60 and 100 W Models: Compliance to EN61000-4-2, 3, 4, 5, 6, 8, 11, EN50204, EN55024, EN61000-6-2, EN61204-3, heavy industry level, criteria A Anemometer | Automation | Accelerometers | Calibrator | Cartridge Heaters | Chart Recorders | Cryogenics | Custom Pressure Transducers | Data Loggers | Data Acquisition | Dial Thermometers | Fiber Optics | Fiber Optic Temperature Measurement | Flexible Heaters | Flow Meters | Glass Bulb Thermometers | Grippers | Heaters | Humidity Measurement | Integrated Circuit Sensors | Immersion Heaters | Infrared Thermometers | Level Measurement | Load Cells | M12 Temperature Connectors | Magnetic Flow Meter | Panel Meter | PID Controllers | pH meter | Pressure Gauges | Pressure Transducers | Pressure Transmitters | Rotameters | RTD | Remote Process Monitoring | Sanitary Sensors | Signal Conditioners | Stepper Motors | Strain Gages | Strip Heaters | Temperature Controllers | Temperature Labels | Temperature Measurement | Temperature Sensor Manufacturing | Temperature Sensors | Temperature Transmitters | Thermal Imagers | Thermistors | Thermocouple | Thermocouple Wire | Thermowell | Ultrasonic Flow Meters | Vortex Flow Meter | Wireless Sensors