Your Source for Process Measurement & Control
UK
44-796-072-6366
Germany
49-178-631-1266
DIN Rail Mount Circuit Breakers
R Series UL1077 Supplementary Protectors
PLACE ORDER - DIN Rail Mounted
- 17.5 mm (0.69") Width per Pole
- Thermal Magnetic Overcurrent Protection
- 0.5 - 60 A, 480Y/277 Vac, 50/60 Hz
- 10 kA Short Circuit Interrupting Capacity
- UL Recognized E137915
- Dual Connection Terminals, Box Clamp and Ring Tongue/Forked Terminals
- Marking Area with Clear Cover
Description
Description
While UL489 branch circuit breakers protectfeeder or branch circuits, R Series UL1077supplementary protectors are made to tripfaster than a standard UL489 circuit breaker,therefore providing additional protection forspecific devices. Supplementary protectorsprovide critical protection in applicationswhere branch circuit protection is not required,or is already provided by a separate device.
R Series supplementary protectors areavailable in one, two, and three-poleconfigurations and up to 20 different currentratings from 0.5A to 60A and can safelybe used in applications up to 480Y/277Vac with a 10 kA short circuit withstandRating.
Three different trip characteristics, including B, C and D curves,give you the ability to configure the exactprotection scheme you require.
B-Trip Protectors
Include business equipment, wiringprotection, lighting, appliances, controlcircuits and some electronic applications.Relatively long thermal trip delay but lowmagnetic trip point.
C-Trip Protectors
Include lighting, wiring protection,appliances, business equipment, and controlcircuit applications. Relatively long thermaltrip delay and medium magnetic trip point.
D-Trip Protectors
Include control transformers, power suppliesand reactive loads. Relatively long thermaltrip delay and very high magnetic trip point.
Features Provided by the Different Types of Circuit Breakers
UL1077 Recognized Supplementry Protectors
 Overload Protection
UL508 Listed Manual Motor Controllers
 Overload Protection
 Switching Function
 Disconnect Function
UL489 Miniature Molded Case Circuit Breakers
 Overload Protection
 Switching Function
 Disconnect Function
 Short Circuit Protection
Specifications
Voltage Rating: 480Y/277 Vac
Short Circuit Withstand Rating (UL - Ratings):
0.5-10A (RC): 10kA with no back-up fuse
12-60A (RC): 10kA with UL-listed Class J back-up fuse; 5kA with no back-up fuse
Calibration Temperature: 30°C (86°F)
Operating Temperature: -25 to 55°C (-13 to 131°F)
Storage Temperature: -40 to 70°C (-40 to 158°F)
Terminal Size Acceptability:
Top: 18-3 AWG
Bottom: 18-2 AWG (line/load reversible)
Tightening Torque (min/max): 17.7/25 lb-in. (2/2.8 Nm)
Terminal Protection Degree: IP20
Vibration Resistance: ≥15g
Dimensions:
Height: 89.3 mm (3.51")
Width:
One Pole: 17.5 mm (0.69")
2 Pole: 35 mm (1.38")
3 Pole: 52.5 mm (2.07")
Depth:68.4 mm (2.69") from DIN rail
Use the "Part Number Builder" below for product selection. Anemometer | Automation | Accelerometers | Calibrator | Cartridge Heaters | Chart Recorders | Cryogenics | Custom Pressure Transducers | Data Loggers | Data Acquisition | Dial Thermometers | Fiber Optics | Fiber Optic Temperature Measurement | Flexible Heaters | Flow Meters | Glass Bulb Thermometers | Grippers | Heaters | Humidity Measurement | Integrated Circuit Sensors | Immersion Heaters | Infrared Thermometers | Level Measurement | Load Cells | M12 Temperature Connectors | Magnetic Flow Meter | Panel Meter | PID Controllers | pH meter | Pressure Gauges | Pressure Transducers | Pressure Transmitters | Rotameters | RTD | Remote Process Monitoring | Sanitary Sensors | Signal Conditioners | Stepper Motors | Strain Gages | Strip Heaters | Temperature Controllers | Temperature Labels | Temperature Measurement | Temperature Sensor Manufacturing | Temperature Sensors | Temperature Transmitters | Thermal Imagers | Thermistors | Thermocouple | Thermocouple Wire | Thermowell | Ultrasonic Flow Meters | Vortex Flow Meter | Wireless Sensors