Your Source for Process Measurement & Control
UK
44-796-072-6366
Germany
49-178-631-1266
Product Groups
TIMING RELAYS
TRODEKS Engineering | Thermocouples, Pressure Transducers, Flow Meters, PID Controllers
TRFP240AC
PLACE ORDER 
  • 20 Time Ranges and 10 Timing Functions
  • Time Delays from 0.1 sec to 600 hrs
  • Space-Saving, Compact Package
  • High Repeat Accuracy of ±0.2%
  • LED Indication
  • 2 Form C DPDT Delayed Output Contacts
  • 10 A Contact Rating
 Manuals (contact with email : [email protected])
 Print
Description

Description

The TR Series Timing Relays are designed tomeet most timing requirements by offeringmore flexibility in range of input voltage,timing range and functionality. Use a rotaryswitch to choose from 20 selectable timeranges from 0.1 second to 600 hours. Weoffer both a power triggered and signaltriggered model—each with expandedoperation modes. There is a green LED toindicate when power is ON and an orangeLED when output is ON.

SPECIFICATION
Contact Configuration: 2 Form C, DPDT (delayed output)
Allowable Voltage/Current: 240 Vac, 30 Vdc/10 A
Max Permissible Operating Frequency: 1800 cycles per hour
Rated Resistive Load: 10 A, 240 Vac/ 30 Vdc
Rated Inductive Load: 7 A, 240 Vac/ 30 Vdc
Horsepower Rating: 1.6 hp 120 Vac, 1.3 hp 240 Vac
Electrical Life: 500,000 operations min (resistive)
Mechanical Life: 50,000,000 operations minimum
Operation System: Solid-state CMOS circuit
Time Range: 0.1 sec to 600 hours
Coil Rating: 100-240 Vac
Triggering: By signal
Pollution Degree: 2 (IE60664-1)
Overvoltage Category: III (IE60664-1)
Rated Operational Voltage: 100 to 240 Vac (50/60 Hz)
Voltage Tolerance: 85 to 264 Vac (50/60 Hz)
Input OFF Voltage: Rated Voltage x 10% minimum
Ambient Operating Temperature: -20 to 65°C (-4 to 149°F)
Reset Time: 100 mS maximum
Repeat Error: ±0.2%, ±20 mS
Voltage Error: ±0.2%, ±20 mS
Temperature Error: ±0.5%, ±20 mS
Setting Error: ±10% maximum
Insulation Resistance: 100 M&trodeks; minimum (500 Vdc)
Dielectric Strength Between Power and Output Terminals: 2000 Vac, 1 minute
Dielectric Strength Between Contacts of Different Poles: 2000 Vac, 1 minute
Dielectric Strength Between Contacts of Same Pole: 1000 Vac, 1 minute
Vibration Resistance: 10 to 55 Hz amplitude 0.5 mm; 2 hrs in each of 3 axes
Shock Resistance: 10 G (operating extremes), 40 G (damage limits 3x in each of 3 axes)
Power Consumption (Approx): 6.5 VA @ 120 Vac/60 Hz, 11.6 VA @ 240 Vac/60 Hz
Dimensions: 40 H x 36 W x 77.9 mm D (1.58 x 1.42 x 3.07")
Weight: 89 g (3 oz)
Anemometer  |   Automation  |   Accelerometers  |   Calibrator  |   Cartridge Heaters  |   Chart Recorders  |   Cryogenics  |   Custom Pressure Transducers  |   Data Loggers  |   Data Acquisition  |   Dial Thermometers  |   Fiber Optics  |   Fiber Optic Temperature Measurement  |   Flexible Heaters  |   Flow Meters  |   Glass Bulb Thermometers  |   Grippers  |   Heaters  |   Humidity Measurement  |   Integrated Circuit Sensors  |   Immersion Heaters  |   Infrared Thermometers  |   Level Measurement  |   Load Cells  |   M12 Temperature Connectors  |   Magnetic Flow Meter  |   Panel Meter  |   PID Controllers  |   pH meter  |   Pressure Gauges  |   Pressure Transducers  |   Pressure Transmitters  |   Rotameters  |   RTD  |   Remote Process Monitoring  |   Sanitary Sensors  |   Signal Conditioners  |   Stepper Motors  |   Strain Gages   |   Strip Heaters  |   Temperature Controllers  |   Temperature Labels  |   Temperature Measurement  |   Temperature Sensor Manufacturing  |   Temperature Sensors  |   Temperature Transmitters  |   Thermal Imagers  |   Thermistors  |   Thermocouple  |   Thermocouple Wire | Thermowell  |   Ultrasonic Flow Meters  |   Vortex Flow Meter  |   Wireless Sensors