Your Source for Process Measurement & Control
UK
44-796-072-6366
Germany
49-178-631-1266
RTD In-Head Temperature Transmitter
TX12
PLACE ORDER - User Trim—Null Out Sensor Error
- Unique Push Button Configuration Without PC
- High Stability
- Programmable Burnout
- LED Sensor Fail Indicator
- Reconfigure in Seconds
Description
Description
The TX12 head mountedtemperature transmitter connectsto any standard pt100 resistancesensor and converts the linearizedtemperature to a 4 to 20 mA signal.The transmitter is a two wire device,and is fully configurable by the user,over a wide temperature range, withthe aid of a simple push button. Thisnew TX12 design incorporatesadditional configuration menus,allowing the user to push button trimthe transmitter output at both zeroand span, ideal for trimming outsensor errors. The transmittersadvanced circuitry guaranties highstability over the wide operatingambient temperature rangesexperienced by head mounteddevices.One of the transmitters features isthe program LED, which providesvisual indication of sensor faultwhen in normal operation and isalso used to guide the operatorthrough the simple menus duringconfiguration.
SPECIFICATIONS
Input
Sensor Type: Pt100 100 Ω @ 0°C 2 or 3 Wire
Sensor Range: -200 to 850°C (-328 to 1562°F)
Sensor Connection: Screw terminal
Minimum Span: 25°C (77°F)
Linearisation: BS EN 60751(IEC 751) standard/JISC 1604
Measurement Accuracy: 0.1°C ±0.05% of reading
Thermal Drift: 25 ppm/°C
Excitation Current: <200 uA
Lead Resistance Effect: 0.002°C/Ω
Maximum Lead Resistance: 20 Ω per leg
Output
Output Type: 2 wire, 4 to 20 mA current loop
Output Range: (4.0 to 20.0) mA
Output Connection: Screw terminal
Maximum Output: 21.5 mA (in high burnout condition)
Minimum Output: 3.8 mA (in low burnout condition)
Accuracy: (mA output /2000) or 5 uA (whichever is the greater)
Loop Voltage Effect: 0.2 uA/V
Thermal Drift: 1 uA /°C
Maximum Output Load: [(Vsupply-10)/20]K Ω
(Example: 700 Ω @ 24V)
General Specifications
Update Time: 500 mS
Response Time: 1 second
Start Up Time: 4 seconds (I out < 4 mA during start up)
Warm-Up Time: 1 minute to full accuracy
Power Supply: 10 to 30 Vdc
Environmental
Ambient Operating Range: -40 to 85°C (-40 to 185°F)
Ambient Storage Temperature: -50 to 90°C (-58 to 194°F)
Ambient Humidity Range: 10 to 90% RH non condensing
Physical
Dimensions: 43 diameter; 21 mm height (1.7; 0.8")
Weight: 31 g (0.068 lb) (encapsulated)
Approvals
EMC - BS EN 61326 :1998: Electrical equipment for measurement control and laboratory use
ANNEX A: Immunity test requirements for equipment intended for use in industrial locations
ANNEX F: Test configurations, operational conditions and performance criteria for transducers with integrated or remote signal conditioning
IEC 61000-4-2: Electrostatic discharge
IEC 61000-4-3: EM field
IEC 61000-4-4: Transient burst (output)
IEC 61000-4-5: Surge (output)
Note: Sensor input wires to be less than 3 m to comply. Anemometer | Automation | Accelerometers | Calibrator | Cartridge Heaters | Chart Recorders | Cryogenics | Custom Pressure Transducers | Data Loggers | Data Acquisition | Dial Thermometers | Fiber Optics | Fiber Optic Temperature Measurement | Flexible Heaters | Flow Meters | Glass Bulb Thermometers | Grippers | Heaters | Humidity Measurement | Integrated Circuit Sensors | Immersion Heaters | Infrared Thermometers | Level Measurement | Load Cells | M12 Temperature Connectors | Magnetic Flow Meter | Panel Meter | PID Controllers | pH meter | Pressure Gauges | Pressure Transducers | Pressure Transmitters | Rotameters | RTD | Remote Process Monitoring | Sanitary Sensors | Signal Conditioners | Stepper Motors | Strain Gages | Strip Heaters | Temperature Controllers | Temperature Labels | Temperature Measurement | Temperature Sensor Manufacturing | Temperature Sensors | Temperature Transmitters | Thermal Imagers | Thermistors | Thermocouple | Thermocouple Wire | Thermowell | Ultrasonic Flow Meters | Vortex Flow Meter | Wireless Sensors